EasyManuals Logo
Home>GE>Control Unit>MiCOM P40 Agile

GE MiCOM P40 Agile User Manual

GE MiCOM P40 Agile
802 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #237 background imageLoading...
Page #237 background image
7.11 DISTANCE PROTECTION WORKED EXAMPLE
This section presents a worked example of how to set the Distance protection. For this case study, we assume that
Zone 1 Extension is not used, and that only three zones are required for basic Distance protection (Zones 1 and 2
Forward Directional, and Zone 3 Forward Offset). The following settings are derived:
Line Impedance
Residual Compensation
Zone 1 reach settings for phase-faults and earth-faults
Zone 2 reach settings for phase-faults and earth-faults
Zone 3 reach settings for phase-faults and earth-faults
Zone 3 reverse reach settings
Zone 4 reach settings (for use with Permissive Overreach or Blocking schemes if needed)
Load avoidance
The settings are applicable whether the Distance protection characteristics are set to Mho, or Quadrilateral. If you
choose Quadrilateral however, you will need to consider the Resistive reaches of Quadrilaterals.
For this study, we wish to protect one line of a double 230kV, 100km line between a substation at Green Valley and
a substation at Blue river. There are generating sources at Tiger Bay, 80 km from Green Valley and at Rocky Bay, 60
km from Blue River.
The single-line diagram for the system is shown in the following figure:
Tiger Bay
Green Valley Blue River
Rocky Bay
80 km
100 km
60 km
IED IED
E02705
Figure 99: Example power system
The system data is as follows:
System Voltage: 230kV
System earthing: Solid
CT ratio: 1200 : 5
VT ratio: 230 000 : 115
Line length: 100km
Positive sequence line impedance (Z1): 0.089 + j0.476 ohms/km = 0.484Ð79.4°
Zero sequence line impedance (Z0): 0.426 + j1.576 ohms/km = 1.632Ð74.8°
Z0/Z1: 3.372Ð4.6°
Green Valley substation fault level: 2000 MVA to 5000 MVA
Blue river substation fault level: 1000 MVA to 3000 MVA
Circuit continuous rating: 400 MVA
Worst case power factor of load: 0.85
P543i/P545i Chapter 7 - Distance Protection
P54x1i-TM-EN-1 201

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P40 Agile and is the answer not in the manual?

GE MiCOM P40 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P40 Agile
CategoryControl Unit
LanguageEnglish

Related product manuals