Parameter Name / value range / [default seng] Info
0x4029:004
(P804.04)
Sequencer segment 4: Digital outputs
(Segment 4: Digital outp.)
0 ... [0] ... 255
From version 03.00
Oponally: Set digital outputs to the level set here for the execuon
me of the segment.
Note!
In order that the control of a digital output is executed by the sequencer,
the following assignment must be made for the respecve digital out-
put:
Relay: 0x2634:001 (P420.01) = "Sequencer controlled [100]"
Digital output 1: 0x2634:002 (P420.02) = "Sequencer controlled [100]"
Digital output 2: 0x2634:003 (P420.03) = "Sequencer controlled [100]"
Bit 0 Relay 0 = X9/NO-COM open and NC-COM closed.
1 = X9/NO-COM closed and NC-COM open.
An inversion set in 0x2635:001 (P421.01)is taken into consideraon
here.
Bit 1 Digital output 1 0 = set digital output 1 to LOW level.
1 = set digital output 1 to HIGH level.
An inversion set in 0x2635:002 (P421.02) is taken into consideraon
here.
Bit 2 Digital output 2 0 = set digital output 2 to LOW level.
1 = set digital output 2 to HIGH level.
An inversion set in 0x2635:003 (P421.03) is taken into consideraon
here.
0x4029:005
(P804.05)
Sequencer segment 4: Analog outputs
(Segment 4: Analog outp.)
0.00 ... [0.00] ... 10.00 VDC
From version 03.00
Oponally: Set analog outputs to the voltage value set here for the exe-
cuon me of the segment.
Note!
In order that the control of an analog output is executed by the
sequencer, the following assignment must be made for the respecve
analog output:
Analog output 1: 0x2639:002 (P440.02) = "Sequencer controlled [10]"
Analog output 2: 0x263A:002 (P441.02) = "Sequencer controlled [10]"
0x4029:006
(P804.06)
Sequencer segment 4: PID setpoint
(Segment 4: PID setp.)
-300.00 ... [0.00] ... 300.00 PID unit
From version 03.00
PID control value for the segment.
Only relevant if the PID control in 0x4020:001 (P600.01) is acvated.
0x4029:007
(P804.07)
Sequencer segment 4: Torque setpoint
(Segment 4: Torque setp.)
-400.0 ... [100.0] ... 400.0 %
From version 03.00
Torque setpoint for the segment.
Only relevant for operang mode 0x6060 (P301.00) = "MS: Torque
mode [-1]".
0x4029:008 Sequencer segment 4: NetWordOUT2
0 ... [0] ... 65535
From version 03.00
Oponally: Set the NetWordOUT2 data word to the value set here for
the execuon me of the segment.
The NetWordOUT2 data word 0x400A:002 (P591.02) can be mapped
to a network register to transfer the set value as process date.
0x4029:009 Sequencer segment 4: Reserved
0 ... [0] ... 4294967295
From version 03.00
0x402A:001
(P805.01)
Sequencer segment 5: Frequency setpoint
(Segment 5: Frequency setp.)
-599.0 ... [0.0] ... 599.0 Hz
From version 03.00
Frequency setpoint for the segment.
Only relevant for operang mode 0x6060 (P301.00) = "MS: Velocity
mode [-2]".
Direcon of rotaon according to sign.
0x402A:002
(P805.02)
Sequencer segment 5: Acceleraon/deceleraon
(Segment 5: Accel./decel.)
0.0 ... [5.0] ... 3600.0 s
From version 03.00
Acceleraon/deceleraon for the segment.
Only relevant for operang mode 0x6060 (P301.00) = "MS: Velocity
mode [-2]".
The set me refers to the acceleraon from standsll to the set maxi-
mum frequency. The deceleraon is eected with the same ramp.
0x402A:003
(P805.03)
Sequencer segment 5: Time
(Segment 5: Time)
0.0 ... [0.0] ... 100000.0 s
From version 03.00
Runme for the segment aer the expiry of which it is switched over to
the next step of the sequence.
Only relevant for Sequencer mode 0x4025 (P800.00) = "Time opera-
on [1]" or "Time & step operaon [3]".
With the seng "0.0", the segment will be skipped.
Sequencer
Segment conguraon
510

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals