Line Modules Booksize
4.2 Active Line Modules with internal air cooling
Booksize Power Units
170 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Table 4- 10 Technical data of Active Line Modules
7TE25–5AA3 +
Active Interface
Module
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
1)
kW (P
n
)
kW (P
s6
)
16
21
36
47
55
71
55
71
Continuous regenerative power
kW
16
36
55
55
Line voltage
Line frequency
V
ACrms
Hz
3 AC 380 … 480 ± 10 % (-15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
DC
510 … 720
820 ± 2 %
Rated input current:
for AC 400 V
Input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
A
AC
A
AC
A
AC
AC
25
26 / 21
32
55
58 / 46
71
84
88 / 70
108
84
88 / 70
108
Rated DC link current:
for 600 V
DC link current:
for 600 V DC; for S6 - 40 %
for 600 V DC; peak current
A
DC
A
DC
27
35
60
79
92
121
92
121
Current carrying capacity
DC link busbars
Reinforced DC link busbars
A
DC
A
DC
DC
100
150
200
--
200
--
200
--
Electronics current drawn
at 24 V DC
(including electronics losses, see
Power loss tables (Page 781))
W 282.8 666 945.6 945.6
without derating
° C
40
40
40
40
Active Line Module
μF
705
1410
1880
1880