Line Modules Booksize
4.10 Smart Line Modules with cold plate
Booksize Power Units
340 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Help with the mechanical control cabinet design is available from:
Siemens AG
Industry Sector, IA DT MC MF - WKC AS
TCCCC (Technical Competence Center Cabinets Chemnitz)
Postfach 1124
09070 Chemnitz, Germany
E-mail: cc.cabinetcooling.aud@siemens.com
Properties of the heat sink
We recommend using AlMgSi 0.5 as the heat sink material.
The roughness of the external heat sink surface should be at least Rz 16 and the contact
surface between the heat sink and cold plate should have an evenness of 0.2 mm.
acturers can adapt the heat sink version to their special requirements. The
specified rated data for the Power Modules can only be achieved if the power losses can be
dissipated by the external heat sink under the specified general conditions.
Damage to the cold plate caused by incorrect mounting
The screw bolts can be damaged when mounting the cold plate.
• Do not damage the cold plate.
Table 4- 91 Technical data for Smart Line Modules with cold plate cooling
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
1)
kW (P
n
)
kW (P
S6
)
max
5
6,5
10
13
Continuous regenerative power
Peak regenerative power
kW
5
10
Line voltage
Line frequency
V
AC
Hz
DC
3 AC 380 … 480 ± 10 % (-15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
V
DC
V
DC
510 … 720
820 ± 2 %
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com