Line Modules Booksize
4.7 Basic Line Modules with cold plate
Booksize Power Units
264 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
4.7.6
Mounting
Please note the following before mounting a Basic Line Module with cold plate onto a
customer-specific heat sink:
Before mounting, check the surface of the heat sink to ensure that it is not damaged.
To improve heat transfer, a heat-conducting medium must be used. Special spherical-
indented heat-conducting foil must be used for this purpose. Every Basic Line Module
cold plate is supplied with heat-conducting foil cut to the right size. Note the mounting
position of the heat-conducting foil (see figures below).
Note
Also replace the heat-conducting foil when replacing a component.
Only use heat-conducting foil released or supplied by Siemens.
Table 4- 61 Overview of heat-conducting foils
Order number
Heat-conducting foil, 100 mm
6SL3162-6FD00-0AA0
Heat-conducting foil, 150 mm
6SL3162-6FF00-0AA0
Heat-conducting foil, 200 mm
6SL3162-6FH00-0AA0
Note
M6 studs and hexagon nuts or grub screws (ISO 7436
-M6x40-14 H, property class 8.8) are
recommended for mounting the components.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6SL3120-2TE21-0AA3 and is the answer not in the manual?

Siemens 6SL3120-2TE21-0AA3 Specifications

General IconGeneral
BrandSiemens
Model6SL3120-2TE21-0AA3
CategoryPortable Generator
LanguageEnglish

Related product manuals