Line Modules Booksize
4.7 Basic Line Modules with cold plate
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
269
Table 4- 62 Technical data for Basic Line Modules with cold plate cooling
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
1)
kW (P
n
)
kW (P
S6
)
20
26
40
52
100
130
Continuous power
kW (P
n
)
max
5
10
-
Line voltage
Line frequency
V
ACrms
Hz
3 AC 380 … 480 ± 10 % (-15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
DC
510 … 720
820 ± 2 %
at AC 380 V
at AC 480 V / AC 528 V
at 480 V; S6 - 40 %
A
AC
A
AC
A
AC
AC
34,5
31 / 29
38
69
62 / 58
78
172
154 / 145
193
Rated DC link current:
for 600 V
DC link current:
for 540 V
for DC 600 V; S6 - 40 %
for DC 600 V; peak current
A
DC
A
DC
A
DC
33,5
37
43
67
48
87
167
185
217
Current carrying capacity
DC link busbars
Reinforced DC link busbars
A
ACrms
A
ACrms
ACrms
100
150
200
--
200
--
Electronics current drawn
at 24 V DC
(including electronics losses, see Power
loss tables (Page 781))
W 141,6 276,4 618,4
Basic Line Module
μF
940
1880
4100
3)
Circuit breaker
(IEC 60947 and UL)
See Section Overcurrent protection using line fuses and
circuit breakers (Page 51)
Rated short-circuit current
4)
kA 65 65 65
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com