Line Modules Booksize Compact
5.1 Smart Line Modules Booksize Compact
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
351
Table 5- 1 X1 line connection
Supply voltage:
3 AC 380 … 480 V, 50 / 60 Hz
Type: Screw terminal 7 (Page 755)
Max. cross-section that can be connected: 16 mm
2
Tightening torque: 1.5 … 1.8 Nm
W1
PE connection Threaded hole M5 / 3 Nm
1
1)
For ring cable lugs without insulation
Table 5- 2 X21 EP terminal / temperature sensor
Temperature sensors: KTY 84–1C130
1)
/ PTC
1)
/bimetallic switch with NC contact
The temperature sensor type and the temperature
display can be selected via parameter and read-out.
2)
2 - Temp
Voltage: 24 V DC
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H: 100 μs
4 EP M (Enable Pulses)
Type: Screw terminal 1 (Page 755)
Max. cross-section that can be connected 1.5 mm
2
:
The temperatures are detected but not evaluated in the Smart Line Module.
2)
For further information see SINAMICS S120, Commissioning Manual