Line Modules Booksize
4.4 Active Line Modules with cold plate
Booksize Power Units
212 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Table 4- 33 Technical data for Active Line Modules with cold plate cooling
25-5AA3 +
Active
Interface
Module
1)
1)
Rated power (S1)
2)
Infeed power
(S6 - 40 %)
2)
2)
kW (P
n
)
kW (P
s6
)
16
21
36
47
55
71
55
71
80 (64)
1)
106 (85)
1)
120 (84)
1)
145 (116)
1)
Continuous regenerative
power
kW
kW
16
35
36
70
55
91
55
110
80 (64)
1)
131
120 (84)
1)
175
Line voltage
Line frequency
V
ACrms
Hz
3 AC 380 … 480 ±10 % (- 15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
Undervoltage trip
3)
V
DC
V
DC
V
DC
510 … 720
820 ± 2 %
360 ± 2 %
Rated input current:
for AC 400 V
Input current:
for AC 380 V
for AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
A
AC
A
AC
A
AC
A
AC
AC
25
26
21
32
55
58
46
71
84
88
70
108
84
88
70
108
122 (98)
1)
128 (102)
1)
102 (82)
1)
161 (129)
1)
182 (127)
1)
192 (134)
1)
152 (106)
1)
220 (154)
1)
Rated DC link current:
for 600 V
DC link current:
for 600 V DC; for S6 - 40 %
for 600 V DC; peak current
A
DC
A
DC
27
35
60
79
92
121
92
121
134 (99)
1)
176 (141)
1)
200 (140)
244 (171)
1)
Current carrying capacity
DC link busbars
Reinforced DC link busbars
24 V DC busbars
A
ACrms
A
ACrms
ACrms
100
150
200
--
200
--
200
--
200
--
200
Electronics current drawn
at 24 V DC
DC
(including electronics
losses, see Power loss
tables (Page 781))
W 280.4 655.2 927.6 927.6 1383.6 2243.2