Figure 8-5 Display of a threshold 2 error message with two columns (maintenance demanded)
Figure 8-6 Display of a threshold 3 error message with three columns (maintenance alarm)
The factory setting is 'OFF'.
See also
Monitoring the position average value 'P.\\PAVG' (Page 185)
8.3.2.23 '51.FSTY' Safety position
Possible settings: FSVL
FSSP
FSAC
Purpose: Use this parameter to move the actuator to a defined safety position
when communication fails.
Description: Three settings are available:
FSVL:
the actuator is controlled using the configured safety setpoint.
This value also becomes effective following failure of the
auxiliary power supply.
FSSP:
the actuator is controlled using the last effective setpoint.
FSAC:
the positioner responds as described in "Reaction to failure of
auxiliary powers (Page 94)."
Fail in Place The following must be observed when using the "Fail in Place" func‐
tion:
The "51.FSTY" parameter must be set to "FSSP" so that the posi‐
tioner retains the current position even following switching on again.
Factory setting: FSAC
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC 161

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2
CategoryValve Positioners
LanguageEnglish

Related product manuals