J4.LEVL3 - threshold 3
Adjustment range: -40.0C ... 90.0C
-40.0F ... 194.0F
Purpose: Use this sub-parameter to set the temperature for threshold 3.
The positioner triggers a threshold 3 message if the current tem‐
perature inside the enclosure exceeds threshold 3. The process to
activate and display this message is described in the 'XDIAG' pa‐
rameter.
Factory setting: 90.0C
8.3.3.10 Monitoring of number of total strokes 'L.\\STRK'
L. STRK - Monitoring of number of total strokes
Condition: The '50.XDIAG' Activation of extended diagnostics (Page 160) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
Possible settings: ● OFF
● On
Purpose: Use this parameter to continuously monitor the total strokes cov‐
ered by the actuator. A total stroke corresponds to the path from the
lower endstop of the actuator to the upper endstop and back again,
in other words twice the travel. During operation, partial strokes of
the actuator are added together into total strokes. Monitoring is
performed in three steps. To activate monitoring, set the parameter
to 'On'. Sub-parameters are displayed. Appropriately set the sub-
parameters.
The current value is displayed in Diagnostic value '1.STRKS - Num‐
ber of total strokes' (Page 259). The positioner triggers a message
if the current value exceeds one of the three thresholds. This mes‐
sage is only output if threshold 2 or 3 is not exceeded at the same
time.
Factory setting: OFF
L1.LIMIT - Limit
Adjustment range: 1 ... 1.00E8
Purpose: Use this sub-parameter to set the base limit for the number of total
strokes. Set the base limit in a range from '1' to '1.00E8'.
Factory setting: 1.00E6
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
182 Operating Instructions, 05/2019, A5E00127926-AC