12.2.4.18 Diagnostic value '20.PAVG - Average value of position'
Indication on the display: ● OFF
● IdLE
● rEF
● COMP
Purpose: This value shows the last calculated comparison average. Meaning
of the displays:
● OFF: The underlying function is deactivated in the configuration
menu.
● IdLE : Inactive. The function has not been started yet.
● rEF: The reference average is calculated. The function was
started, and the reference interval is in progress at the moment.
● COMP: The comparison average is calculated. The function
was started, and the comparison interval is in progress at the
moment.
12.2.4.19 Diagnostic value '21.P0 - Potentiometer value of lower endstop (0%)' / '22.P100 -
Potentiometer value of upper endstop (100%)'
Display range: ● NO
● 0.0 ... 100.0
'NO': Changing the low or upper endstop is not possible in the cur‐
rent state of the control valve. Initialize the positioner again.
Condition 1 -
read values
The positioner is initialized.
Purpose 1 Read values
You can use the P0 and P100 parameters to read the values for the
lower endstop (0%) and the upper endstop (100%) of the position
measurement as determined during the automatic initialization. The
values of manually approached end positions are applicable for
manual initialization.
Condition 2 -
change values
● The positioner is initialized and in manual mode (MAN) or
automatic mode (AUT).
● The current position of the actuator is within the range -10% to
+10% of the lower endstop (P0).
● The current position of the actuator is within the range 90% to
110% of the upper endstop (P100).
Diagnostics and troubleshooting
12.2 Diagnostics
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC 265