Positioner, modules and position detection sys‐
tems
Temperature class T4 Temperature class T6
● Already fitted:
6DR5ayb-0cdef-g.Ah-Z ...
for f = 1, 3
● Can be retrofitted 6DR4004-6J
-30 °C ≤Ta ≤ +80 °C -
● Already fitted and can be retrofitted:
6DR5ayb-0cdef-g*Ah-Z M40
for f = 1, 3
-40 °C ≤Ta ≤ +80 °C -
Position detection systems
● Non-Contacting Sensor (NCS)
6DR4004-6N**-0-***
-40 °C ≤Ta ≤ +90 °C -40 °C ≤Ta ≤ +70 °C
● External position detection system in the
polycarbonate enclosure with potentiometer
C73451-A430-D78
-40 °C ≤Ta ≤ +90 °C -40 °C ≤Ta ≤ +60 °C
● External Position Transmitter (Potentiometer)
6DR4004-1ES
-40 °C ≤Ta ≤ +90 °C -40 °C ≤Ta ≤ +60 °C
● External Position Transmitter (NCS)
6DR4004-2ES
-40 °C ≤Ta ≤ +90 °C -40 °C ≤Ta ≤ +50 °C
13.6 Certificates, approvals, explosion protection
Certificates and approvals
Classification according to pressure equip‐
ment directive (PED 2014/68/EU)
For fluid group 1 gases; fulfills requirements according to article 4, paragraph 3
(good engineering practice SEP)
CE conformity The applicable directives and applied standards with their revision levels can be
found in the EU declaration of conformity on the Internet.
UL conformity You can find the appropriate "Standard(s) for Safety", including the relevant
versions, in the UL-CERTIFICATE OF COMPLIANCE on the Internet.
13.7 Electrical specifications
Basic device without
explosion protection
Basic device with ex‐
plosion protection
Ex d
Basic device with ex‐
plosion protection
Ex "ia"
Basic device with ex‐
plosion protection Ex
"ic", "ec", "t"
Auxiliary power supply bus cir‐
cuit
Bus-powered
Bus voltage 9 ... 32 V 9 ... 32 V 9 ... 24 V 9 ... 32 V
For connecting to circuits with
the following peak values
Technical data
13.7 Electrical specifications
SIPART PS2 with PROFIBUS PA
286 Operating Instructions, 05/2019, A5E00127926-AC