Alarm, error, and system messages
7.5 Wizard-based error messages
Operating with the Local User Interface
Operating Manual, 06/2017, A5E31930478-05
273
Wizard-based error messages
Overview
The following tables include descriptions of errors which may occur when executing wizard-
based processes. The wizard-based procedures especially include calibrations and AutoCal
procedures.
Note
Representation of wizard-based error messages in the logbook
Errors which prevent starting the wizard do not generate an entry in the logbook.
Errors which occur during execution of a wizard generate an entry in the logbook. However,
only the corresponding error nu
mber is entered in this case, not the message text.
Table 7- 8 Wizard-based error messages (F1001, ... , F1031)
Message text (cause/remedy)
F1006 "F1006: The redetermined zero point and span
point deviate too much from the last zero point
and span point determined. The maximum per-
mitted deviation is set in the menu Calibration
tolerance. Possible causes:
1. An incorrect gas,
2. Faulty switching of the solenoid valves,
3. Different reference gas without new standardi-
zation or
4. A faulty analyzer module."
F1007
"F1007: The measured or calculated parameter is
outside of the permitted min/max limits. Check
your entries and setpoints."
F1008
"F1008: The gas flow is too low.
Check to see if the gas bottle is open or if the
correct valve is connected and turned on."
"F1009: Incorrect calibration gas detected."
F1010 "F1010: There are active errors. Correct the
pending errors and restart the wizard."
"F1012: Internal error occurred."
F1013 "F1013: A component could not be found. The
wizard cannot be started."
F1014 "F1014: The calibration type does not match the
selected components. Check the selection of
components or change the calibration type."
F1015, ... , F1017 "F101n: Internal error occurred. The wizard can-