Unit Test
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 103
6.3 Testing Alarm Zones
This manual test activates all Fire Alarm Devices (FAD) in a selected
alarm zone (with audible indication).
The duration of the signal and the interval between each signal is 1
second ON and 7 seconds OFF. The test signal is given the lowest
priority. In the event of an alarm, the alarm signal will thus override
the test signal.
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Test, then press Enter.
Scroll down to Alarm Zone, then press Enter.
Use the arrow button to select the Alarm Zone that
is to be tested. Use, if necessary, the multiselect feature to select
several alarm zones.
(To view detailed information for one selected alarm zone before
testing, you can press Enter, then return to the previous level by
pressing the Cancel button
).
Press the Function button
To start the test, press Enter.
Press Enter once more to confirm.
To stop the test, use the arrow up/down button to select the
alarm zone(s) that is set to test mode, press the Function button
, use the arrow down button to select Stop Test, then press
Enter twice.