Unit Test
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 104
6.4 Testing Fire Alarm Devices
This chapter describes how to test each Fire Alarm Device (FADs)
individually.
When the test is initiated for a selected Fire Alarm Device (FAD), a
test signal will be sent to this FAD.
The duration of the signal and the interval between each signal is 1
second ON and 7 seconds OFF. The test signal is given the lowest
priority. In the event of an alarm, the alarm signal will thus override
the test signal.
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Test, then press Enter.
Scroll down to Fire Alarm Devices, then press Enter.
Use the arrow button to select the Fire Alarm Device (FAD) that
is to be tested.
(To view detailed information for the selected Fire Alarm Device
before testing, you can press Enter, then return to the previous level
by pressing the Cancel button
).
Press the Function button
To start the test, press Enter.
Press Enter once more to confirm.
To stop the test, use the arrow up/down button to select the Fire
Alarm Device that is set to test mode, press the Function button
, use the arrow down button to select Stop Test, then press
Enter twice.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autroprime 2 and is the answer not in the manual?

Autronica Autroprime 2 Specifications

General IconGeneral
BrandAutronica
ModelAutroprime 2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals