Loop Operation
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 31
4.4 Change Disable Time Span
This menu selection allows a technician to change the disable time
span.
From the Service Menu, perform the following:
After pressing the Function button for the selected detection
loop(s), use the arrow down button to select Change Disable
Time Span, then press Enter twice.
Enter the hours and minutes, then press Enter.
To confirm the new disable time span, press Enter once more.
The display will return to the list of loops.
4.5 Show Polluted Detectors
This menu selection allows you to specify a limit (default 80) for
black and white dust pollution. All units exceeding the specified limit
will be listed in the display.
The menu also allows you to reset the compensation level for units
exceeding the limit.
From the Service Menu, perform the following:
After pressing the Function button for the selected detection
loop(s), use the arrow down button to select Show Polluted
Detectors, then press Enter twice.
Use the alpanumeric keypad to specify a limit for dust pollution,
then press Enter.
To confirm the setting, press Enter once more.
All points that exceed the specified limit are listed.
To reset the compensation level for a point exceeding the
specified limit, select the point, then press the Function
button
.
Select Reset Compensation Level, then press Enter.
To confirm the setting, press Enter once more.