Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 83
5.11.3 Configure Mimic Inputs and Outputs
From the Mimic Panels Menu (5.11.1), perform the following:
After pressing the Function button for the selected mimic panel(s),
the command Mimic Boards (Mimic Drivers, BUR-200) will
appear, then press Enter.
To access available functions for the Mimic Board, press
the Function button
The following alternatives will appear:
Mimic Input Units
Mimic Output Units
Use the arrow down button to select either Mimic Input Units or
Mimic Output Units, then press the Function button
once
more.
The following commands will appear:
Connect to Output
Connect to Alarm Zone
Disconnect from Output
Disconnect from Alarm Zone
Show Connected Units