Configuration Examples
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 122
9.2.5 Site-specific Configuration – Example 1
Step 1: Create Detection Zones and connect the points (loop
units) to the Detection Zones (5.4.3)
Note that the electronic sounders (Fire Alarm Devices, FADs) in
this example are not to be connected to detection zones.
Add a site-specific name to each address (point) if needed (see
chapter 9.2.7). For example, you can add CANTEEN to address
A1001 (the name will appear as A1001 CANTEEN in the display if
an event occurs). (5.4.2).
Step 2: Connect the new detection zones to the alarm zone
(5.2.3)
The new Detection Zones, DZ1, DZ2, DZ3 and DZ4 have to be
connected to the Alarm Zone (Default Alarm Zone).
Step 3: Save the configuration and restart the system (3.2
and 3.3)
When the site-specific configuration is completed, you have to
save the new configuration and restart the system (refer to
chapter 9.2.4).
In this example, only one Alarm Zone is defined. By default, all
Fire Alarm Devices are connected to the one default Alarm Zone.
Therefore, no configuration is required (you do not have to
connect Fire Alarm Devices to the Alarm Zone). Refer to chapter
5.5.3
In this example, all points activate outputs to Fire Alarm Devices
(FAD), Fault Warning Routing Equipment (FWRE) and Fire Alarm
Routing Equipment (FARE). As this specific functionality already
is provided by the default configuration, no configuration is
required.
Refer to chapter 5.2.4, 5.4.4 and 5.6.
Step 1, Step 2 and Step 3 have to be carried out in this example.