2 Equipment Description
2.28 UCN Node Address Pinning
168 HPM High-Performance Process Manager Service R688
Honeywell December 2020
Zero-ohm jumper method
To use zero-ohm resistors to configure the UCN node address, unplug, discard, or store all the plug
jumpers as noted above. As an example in the following figure, to configure a High-Performance Process
Manager for a UCN node address of 11, do not remove the resistors at the 1, 2, and 8 (1 + 2 + 8 = 11)
positions. Because an odd number of resistors are required, the P (parity) jumper must be removed along
with those at positions 4, 16, and 32. Use a diagonal cutter to clip out the unwanted resistors.
Figure 81 UCN Node Address Pinning Using Zero-Ohm Resistors