2 Equipment Description
2.11 Serial Interface IOP (SI)
R688 HPM High-Performance Process Manager Service 67
December 2020 Honeywell
Model MU-TSIM12 interconnections
The following figure illustrates the Serial Interface configuration.
Figure 12 Model MU-TSIM12 Serial Interface FTA Interconnections
A-size
Card File
Model
MU-TLPA02
Power
Adapter
Model MU-KFTAxx IOP to FTA Cable
(Internal to Cabinet)
or
Model MU-KFTSxx IOP to FTA Cable
(External to Cabinet for CE Compliance)
[50 meters (164 feet) Maximum Length]
Model MU-KLAMxx Internal Cabinet Cable
or
Model MU-KLXxxx External Cabinet Cable
[305 meters (1000 feet) Maximum Length]
UNIT 0 UNIT 1
Model MU-PSIM11
Serial Interface
IOP
A-size
Model
MU-TSIM12
Serial
Interface
FTA
Modbus
Protocol
Device
Device 1
Modbus
Protocol
Device
Device 2
Modbus
Protocol
Device
Device 15
Modbus
Protocol
Device
Model
MU-TSIM12
Serial
Interface
FTA
6582
Customer Supplied
EIA-232 (RS-232) Interface Cable
[15 meters (50 feet Maximum Length]
EIA-422/485 (RS-422/485) Interface Cable
[305 meters (1000 feet Maximum Length]
See note.
Note:
Total maximum length can be up to 1200 meters
(4000 feet) when using the appropriate type of cable.