3 UCN Status Displays
3.4 Display Operation
R688 HPM High-Performance Process Manager Service 193
December 2020 Honeywell
OFFNET
(Text color – red)
The HPM is not responding on the UCN because 1) it
does not exist, 2) power is off, or 3) there is a
hardware failure that prohibits a response.
PARTFAIL
(Text color – red)
There are one or more Partial failures.
PF_IDLE
(Text color – red)
There are one or more Partial failures and the HPMM
is in the Idle state.
PF_IOIDL
(Text color – red)
There are one or more Partial failures, and at least
one IOP is in the Idle state.
Secondary HPMM status
The possible status of the secondary HPMM is defined in the following table with the color of the text
indicated.
Table 25 UCN Status Display – Secondary HPMM Status
BACKUP
(Text color – blue)
Processing is in progress and the secondary HPMM
database is synchronized with the primary HPMM
database.
BKUP_SF
(Text color – blue)
The HPMM is in the Run state, but has a Soft
failure.
ALIVE
(Text color – yellow)
Power is present, but no database or personality
program is loaded.
BACKUP
(Text color – yellow)
The secondary HPMM is in the Idle state, or its
database is not synchronized with the primary
HPMM.
BKUP_SF
(Text color – yellow)
The HPMM is in the Idle state, but has a Soft failure.