2 Equipment Description
2.29 I/O Link Interface Address Pinning
172 HPM High-Performance Process Manager Service R688
Honeywell December 2020
15-Slot card file redundant HPMM subsystem
When redundant HPMMs are installed in two 15-Slot card files, the first card file must be configured for
I/O Link Interface address zero (0) and the second card file must be configured for I/O Link Interface
address one (1). Any additional I/O card files in the HPM subsystem must be addressed consecutively,
starting at I/O Link Interface address two (2). See the following figure for the location of the jumpers on
the 15-Slot card file.
Figure 84 15-Slot Card File I/O Link Interface Address Pinning
7-Slot card file redundant HPM subsystem
When redundant HPMMs are installed in left and right 7-Slot card files, both 7-Slot card files must be
configured for the same I/O Link Interface address of zero (0) since the left 7-Slot card file contains I/O
slots 3 through 7, and the right 7-Slot card file contains I/O slots 9 through 15. Any additional I/O card
files in the subsystem must be addressed consecutively, starting at I/O Link Interface address one (1).
See Figure 81 for the location of the jumpers on the 7-Slot card files.