3 UCN Status Displays
3.5 HPM Status Displays
R688 HPM High-Performance Process Manager Service 215
December 2020 Honeywell
IOP A status states
The possible status of IOP A is defined in the following table with the color of the text indicated.
Table 36 HPM Status Display – IOP A Status
Term
Definition
BKP
(Text color – blue)
IOP A is currently the secondary IOP and processing in
the IOP is in progress.
OK
(Text color – blue)
IOP A is currently the primary and processing in the IOP
is in progress.
BKP
(Text color – yellow)
IOP A is currently the secondary IOP and in the Idle
state.
IDL
(Text color – yellow)
IOP A is currently the primary IOP, but no processing is
in progress.
BSF
(Text color – red)
IOP A is currently the secondary IOP and processing is
in progress, but a Soft failure has been detected in the
IOP.
CFG
(Text color – red)
The IOP type that occupies this card slot has a
configuration mismatch.
NR
(Text color – red)
IOP A is not responding on the I/O Link Interface.
SF
(Text color – red)
IOP A is currently the primary IOP and processing is in
progress, but a Soft failure has been detected in the IOP.