2 Equipment Description
2.8 IOP Card Files
60 HPM High-Performance Process Manager Service R688
Honeywell December 2020
Low Level Multiplexer IOP (LLMux)
A Low Level Analog Input Multiplexer (LLMux) IOP processes up to 32 inputs from two 16 input
FTAs.
The following figure illustrates LLMux FTA interconnections for non-CE Compliant FTA models. CE
Compliant FTA models are similar. See the Process Manager I/O Installation manual for detailed
information.
Figure 9 Low Level Multiplexer Interconnections
A-Size
Card File
Model
MU-TLPA02
Power
Adapter
The FTA assemblies must
be mounted upright
(mercury-wetted relays) at all
times and installed in the
cabinet or a NEMA 12
mounting box.
UP
UNIT 0 UNIT 1
Model MU-PLAM02
LLMux IOP
Model MU-KFTAxx FTA Cable
[50 meters (164 feet) Maximum Length]
Model MU-KLAMxx Internal Cabinet Cable
or
Model MU-KLXxxx External Cabinet Cable
[305 meters (1000 feet) Maximum Length]
LLMux Models
MU-TAMR02 (RTD)
or
MU-TAMT02/12 (TC)
FTAs
B-Size
2910