iManager NetEco 6000
Device Installation and Commissioning Guide
4 Connecting Monitoring Cables to Devices
Copyright © Huawei Technologies Co., Ltd.
99
BOM
Number
BOM Description
Cable Position
25030393
Electric Cable, 300V/500V, 60227 IEC
53(RVV), 2x0.75mm
2
, Black(2Cores:
Brown, Blue), 6A, Flat Outdoor Cable,
CCC, CE
Cable from the door exit
button to the access controller
4.3.5.2 Setting Monitoring Parameters for the Shengjiu_MS899 Electronic
Door Lock
Prerequisites
A network cable used for monitoring is prepared.
Procedure
Step 1 Connect the RJ45 end of the electronic lock cable to the COM port with 12 V power supply
on the ECC500 collector.
----End
4.3.5.3 Connecting a Monitoring Cable to the Door Status Sensor
Prerequisites
A monitoring cable required is prepared.
Context
When connecting the door status sensor to an ECC500 collector, you need to perform the
following steps to prepare a special monitoring cable.
Procedure
Step 1 Open the door status sensor, connect two cables, as shown in Figure 4-40.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei iManager NetEco 6000 and is the answer not in the manual?

Huawei iManager NetEco 6000 Specifications

General IconGeneral
BrandHuawei
ModeliManager NetEco 6000
CategoryServer
LanguageEnglish

Related product manuals