Step 7 Click Connection Test to start the connection test.
Step 8 After the connection test is successful, click in the toolbar to save the device
information.
----End
6.4.6 Adding a PDU
6.4.6.1 Setting Monitoring Parameters for a PDU8000
Prerequisites
The IP address planned for the PDU8000 is obtained.
The PDU8000 is powered on.
Context
Before connecting the PDU8000 to the NetEco, set monitoring parameters, such as Serial
port baud rate and Serial port address.
Procedure
Step 1 On the display panel of the PDU8000, press Settings.
Step 2 Enter the administrators password for the PDU8000, then press .
The PDU8000 preset user name is admin, and the password is 000001. To protect the access security,
change the password after logging in to the PDU8000 for the first time.
Step 3 Click Communication.
Set Serial port baud rate and Serial port address.
Table 6-42 Parameter description
Indicates the baud rate. The default baud
rate is 9600. Set BaudRate for the collector
port to the same value.
DataBit, StopBit, and Parity for the
PDU8000 cannot be set on the WebUI.
Their values are 8, 1, and None
respectively.
Indicates the device address planned for the
PDU8000. The devices with the same
address cannot connect to the same port.
When creating a PDU8000 on the NetEco,
set Device address to the same value.