iManager NetEco 6000
Device Installation and Commissioning Guide
Copyright © Huawei Technologies Co., Ltd.
Step 2 Enter monitoring parameters of the PDU2000. For the input method, see Table 6-19. For
parameters not mentioned in the table, retain the default value.
Table 6-19 Remarks
Enter the planned PDU2000 IP address.
Enter the planned PDU2000 subnet mask.
Enter the planned PDU2000 gateway.
Address reporting the SNMP
Enter the IP address of the NetEco the
PDU2000 connects to.
----End
6.3.7.2 Creating a RPDU on the NetEco
Prerequisites
You have logged in to the NetEco client.
You have the operation rights for Data Center Planning.
You have created a management domain for the device to be added on the Data Center
Planning page.
Procedure
Step 1 Choose Configuration > Configuration Management > Data Center Planning from the
main menu. The Data Center Planning window is displayed.
Step 2 Select the management domain to add a device.
Step 3 If the management domain is a rack or a DDF, click the management domain and choose
Design under . The page for adding a device is displayed. Otherwise, skip this step.
Step 4 In the lower-left corner of the page, click the drop-down list box in Type and select RPDU.
Step 5 Select the device to be added and drag its icon to the management domain.
To delete a device, click the device and choose Delete under .
Step 6 Specify parameters shown in Figure 6-41 in the right pane based on the following table. The
RPDU complying with the SNMP protocol is used as an example.