6.3.5 Adding a PDU
6.3.5.1 Setting Monitoring Parameters for a PDU8000 (over SNMP)
Prerequisites
You have obtained the IP address planned for the PDU8000.
The PDU8000 is powered on.
Context
Before connecting the PDU8000 to the NetEco, set monitoring parameters, such as the IP
address, subnet mask, and gateway, on the PDU8000.
Procedure
Step 1 Tap Settings on the PDU8000 home screen.
Step 2 Enter the PDU8000 password and tap on the screen.
The preset user name and password for the PDU8000 are respectively admin and 000001. To ensure
access security, change the password upon first login.
Step 3 Tap Communication.
1. Check that IP address assign is set to Manual.
2. Set IP address, Subnet mask, and Gateway as planned.
3. Click SNMP Configuration and enter to the screen.
Figure 6-38 SNMP Configuration
4. In SNMP Config. page, set SNMP Version to SNMPv3, retain SNMP Port default
value 161, and click Submit.
5. Click Add under SNMPv3 User. Set User Name. Set Auth. protocol to SHA, and
specify MD5/SHA and Confirm Password. Set Private protocol to AES, and specify
DES/AES and Confirm Password. After setting the parameters, click OK.
6. In Trap Config. page, click Add, set Trap Des. Address to the IP address of the
NetEco server and set Trap Port to 162. Select SNMP Version to SNMPv3. After
setting the parameters, click OK.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei iManager NetEco 6000 and is the answer not in the manual?

Huawei iManager NetEco 6000 Specifications

General IconGeneral
BrandHuawei
ModeliManager NetEco 6000
CategoryServer
LanguageEnglish

Related product manuals