iManager NetEco 6000
Device Installation and Commissioning Guide
3 Installing Devices
Copyright © Huawei Technologies Co., Ltd.
56
Figure 3-61 Installing a card reader with a keypad
----End
3.8.7 Installing a Exit Button
Procedure
Step 1 Remove the exit button cover using a flat-head screwdriver.
Step 2 Remove screws from the exit button, remove the base, and mark mounting holes using the
base and a marker.
Step 3 Drill holes and install the exit button base.
Step 4 Take out any two of the four core wires and connect them to the NO and COM ports on the
exit button.
Step 5 Route the cable through the cable hole.
Step 6 Reinstall the exit button and the cover.
----End
3.8.8 Installing an In-room Emergency Door Release Button
Context
It is recommended that the product be installed 1.41.6 m close to the equipment room
door and 1.6 m above the floor.
Procedure
Step 1 Remove the emergency door release button.