iManager NetEco 6000
Device Installation and Commissioning Guide
Copyright © Huawei Technologies Co., Ltd.
System
Settings >
NMS
Application >
NetEco >
Communicati
on
Parameters
IP address of the primary NetEco server
NOTE
The NetEco IP address and the ECC800 IP
address must be configured in the same
network to ensure normal connection
between the NetEco and the ECC800.
Link to the
monitoring IP
address
Step 4 Set site configuration parameters on the ECC800 WebUI.
Table 6-47 Site Configuration parameters
System
Settings >
System
Parameters >
Site
Configuration
Sets the user-defined smart module
name.
Set the required system type.
----End
6.5.2.2 Creating an ECC800 Collector on the NetEco
Prerequisites
You have logged in to the NetEco client by web browser
You have created a modular or container in Data Center Planning. For detailed
operations, see Creating a Domain.
The IP address of the NetEco connected has been configured on the ECC800 WebUI.
Procedure
Step 1 Choose Configuration > Configuration Management > Data Center Planning from the
main menu. The Data Center Planning window is displayed.
Step 2 Click in the upper left area of the Data Center Planning page to switch to the Uncreated
Device Information page.