iManager NetEco 6000
Device Installation and Commissioning Guide
Copyright © Huawei Technologies Co., Ltd.
If the network security certificate is encrypted, click Browse behind Select a security
certificate. Then select Enable key password, enter Key password, and enter Confirm key
password.
2. For details about how to replace the security certificate for the NetEco, see the
Replacing a Security Certificate for Connection between NetEco and NE chapter in
the NetEco user manual.
----End
6.4.1.3 Setting SNMP Parameters for the ECC500 V6 Collector
You need to set the SNMP parameters for the ECC500 V6 collector if it connects to the EMS,
as these parameters are needed for setting up the ECC500 V6 collector on the EMS.
Prerequisites
You have obtained the IP address, login user name, and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
Procedure
Step 1 Log in to the WebUI of the ECC500 V6 collector.
Step 2 Choose System Settings > SNMP Settings.
Step 3 Select SNMPv3 as SNMP Version, enter 161 for SNMP Port Number, as shown in Figure
6-45.
Figure 6-45 Setting SNMPv3 parameters (01)
Step 4 Click Add in SNMPv3, as shown in Figure 6-46.