iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Copyright © Huawei Technologies Co., Ltd.
157
6.3.3 Adding a Smart Cooling Product
6.3.3.1 Setting Monitoring Parameters for the Smart Cooling Product
The method of setting monitoring parameters for NetCol5000C-65kW&80kW,
NetCol5000-A035/A042/C025/C030 are the same.
Prerequisites
You have obtained the IP address, subnet mask, and default gateway information planned
for the NetCol.
The NetCol is powered on.
Context
NetCol5000C-65kW&80kW, NetCol5000-A035/A042/C025/C030 smart cooling products
support MODBUS-TCP, MODBUS-RTU, and SNMP protocols. When
NetCol5000C-65kW&80kW,NetCol5000-A042/C025/C030 smart cooling products use
MODBUS-TCP connection, refer to this section for configuration details.
This section uses NetCol5000-A035_V100R002C00 as an example.
Procedure
Step 1 Tap Settings on the NetCol5000-A035_V100R002C00 home screen.
Step 2 Enter the administrator user name and password and tap on the screen.
The preset user name and password for the NetCol5000-A035_V100R002C00 are respectively Admin
and 000001. To ensure the access security, change the password upon first login.
Step 3 Choose Comm Settings > Modbus Settings.
Step 4 Set monitoring parameters.
Table 6-10 Parameter description 1
Parameter
Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei iManager NetEco 6000 and is the answer not in the manual?

Huawei iManager NetEco 6000 Specifications

General IconGeneral
BrandHuawei
ModeliManager NetEco 6000
CategoryServer
LanguageEnglish

Related product manuals