iManager NetEco 6000
Device Installation and Commissioning Guide
Copyright © Huawei Technologies Co., Ltd.
Procedure
Step 1 Choose Configuration > Configuration Management > Data Center Planning from the
main menu. The Data Center Planning window is displayed.
Step 2 Click in the toolbar to access Counter Rename.
Step 3 In the navigation pane on the left, select a device.
Step 4 Click the Counter tab and modify performance counter names.
Step 5 Click Apply.
----End
6.4.2.2 Adding Temperature Sensors
6.4.2.2.1 Setting Temperature Sensor Monitoring Parameters
After connecting a temperature sensor to the AI/DI port on the independent deployment AI/DI
unit of an ECC500 V6 collector, you need to set temperature sensor monitoring parameters on
the web user interface (WebUI) of the collector.
Prerequisites
You have obtained the IP address, and login user name and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
Context
Perform operations described in this section only when the independent deployment
AI/DI unit of the NTC sensor is connected to the communications cards in slot 3 or 4 of
the ECC500 collector.
Temperature sensors can be automatically identified and do not need manual setting.
Procedure
Step 1 Log in to the WebUI of the ECC500 V6 collector.
Step 2 Choose Monitoring > MUE06A1 > Running Parameters > AI/DI_1 Port Settings.
Step 3 Select Enable for AI/DI_1 Sensor.