iManager NetEco 6000
Device Installation and Commissioning Guide
Copyright © Huawei Technologies Co., Ltd.
Set this parameter to the user name added in SNMPv3 on the
WebUI of the device.
Set this parameter to the authentication protocol set on the device.
The default selection is SHA.
Support SHA and MD5 agreement.
Set this parameter to the SHA or MD5 password set on the device.
Set this parameter to the privacy protocol set on the device. The
default selection is AES.
Support CBC_DES, AES128, AES192, and AES256 agreement.
Set this parameter to the AES or DES password set on the device.
NOTE
You are advised to set Authentication Password and Privacy Password to
different values.
Timeout duration for connection test (set to 3s by default)
Step 7 Click Connection Test to start the connection test.
Step 8 After the connection test is successful, click in the toolbar to save the device
information.
----End
6.3.6 Adding a Power Module
6.3.6.1 Setting Monitoring Parameters for TP483000D
Prerequisites
The IP address planned for TP483000D is obtained.
TP483000D has been powered on and is running properly.
Context
Before connecting TP483000D to the NetEco, set the IP address on the large-capacity power
system.
Procedure
Step 1 Choose Setting Wizard > Comm Para on the TP483000D WebUI.
Step 2 Set IP Address, Subnet Mask, and Gateway based on the planned data.
----End