Set this parameter to the user name added in SNMPv3 on the
WebUI of the device.
Set this parameter to the authentication protocol set on the device.
The default selection is SHA.
Support SHA and MD5 agreement.
Set this parameter to the SHA or MD5 password set on the device.
Set this parameter to the privacy protocol set on the device. The
default selection is AES.
Support CBC_DES, AES128, AES192, and AES256 agreement.
Set this parameter to the AES or DES password set on the device.
NOTE
You are advised to set Authentication Password and Privacy Password to
different values.
Timeout duration for connection test (set to 3s by default)
Step 8 Click Connection Test to start the connection test.
Step 9 After the connection test is successful, click in the toolbar to save the device
information.
----End
6.3.7 Adding a RPDU
6.3.7.1 Setting RPDU_HUAWEI_PDU2000-32-1PH-20-4-M2 Monitoring
Parameters
Prerequisites
You have obtained the IP address (factory default: 192.168.1.45) of the PDU2000.
You have installed the hardware and powered on the PDU2000.
A PC with an IP address in the same network segment as that of the PDU2000 is
prepared, and the PC has connected to the PDU2000 over a switch.
You have obtained the planned IP address and subnet mask of the PDU2000.
Context
Set the PDU2000 IP address before you connect the PDU2000 to the NetEco.
Procedure
Step 1 Use a PC with an IP address in the same network segment as that of the PDU2000. Enter
http://192.168.1.45 in the address bar, and press Enter on the keyboard.