5.1 A: Initialization Parameters
186 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
â–  A1-12: Bluetooth ID
No.
(Hex.)
Name Description
Default
(Range)
A1-12
(1564)
Bluetooth ID Sets the password necessary to use Bluetooth to control the drive with a smartphone or tablet. -
(0000 - 9999)
â—† A2: User Parameters
You can register frequently used parameters and recently changed parameters here to access them quickly. You can
show the registered parameters in [User Custom Parameters] in the main menu.
â–  A2-01 to A2-32: User Parameters 1 to 32
No.
(Hex.)
Name Description
Default
(Range)
A2-01 to A2-32
(0106 - 0125)
User Parameters 1 to 32 You can select a maximum of 32 parameters for the drive and set them to parameters A2-01 to A2-32.
The [User Parameters] section of the keypad main menu shows the set parameters. You can
immediately access these set parameters.
Parameters in General-
Purpose Setup Mode
(A1-00 - Z3-16)
Note:
• Settings for A2-01 to A2-32 change when the A1-06 [Application Preset] value changes.
• You must set A1-01 = 1 [Access Level Selection = User Parameters] to access parameters A2-01 to A2-32.
The drive saves these parameters to A2-01 to A2-32.
• The drive saves a maximum of 32 parameters.
Note:
Set A1-01 = 2 [Advanced Level] or A1-01 = 3 [Expert Level] to register the necessary parameters.
• The drive automatically saves changed parameters to A2-17 to A2-32.
Note:
Set A2-33 = 1 [User Parameter Auto Selection = Enabled].
â–  A2-33: User Parameter Auto Selection
No.
(Hex.)
Name Description
Default
(Range)
A2-33
(0126)
User Parameter Auto
Selection
Sets the automatic save feature for changes to parameters A2-17 to A2-32 [User Parameters 17 to
32].
Determined by A1-06
(0, 1)
0 : Disabled: Manual Entry Required
Set User Parameters manually.
1 : Enabled: Auto Save Recent Parms
The drive automatically registers changed parameter A2-17 to A2-32. The drive automatically saves the most recently
changed parameter to A2-17, and saves a maximum of 16 parameters. After the drive registers 16 parameters, when
you save a new parameter, the drive will remove a parameter from the User Parameter list to make space for the new
parameter. The drive removes parameters with First In, First Out.
You can show the registered parameters in [User Custom Parameters] in the main menu.
Note:
In General-Purpose Setup Mode, the drive registers parameters starting with A2-27 because the drive registers parameters A2-26 and lower
by default.

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
BrandYASKAWA
ModelHV600
CategoryDC Drives
LanguageEnglish

Related product manuals