Parameter Details
5
5.11 S: Special Applications
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 375
5.11 S: Special Applications
S parameters set these functions:
• Dynamic Noise Control
• Sequence Run Timers
• PI2 Control
• HAND/OFF/AUTO Mode Operation
• Emergency Override Function
â—† S1: Dynamic Noise Control
The Dynamic Audible Noise Control Function suppresses the output voltage to decrease audible noise.
This function can help you quickly restore output voltage after an impact caused a sudden increase in the time
constant. Dynamic Audible Noise Control is useful in applications where load impact is common. You cannot use b8-
01 = 1 [Energy Saving Control Selection = Enabled] and S1-01 = 1 [Dynamic Noise Control = Enabled] at the same
time.
â–  Set Parameters for Dynamic Noise Control
1. Set S1-01 = 1 [Dynamic Noise Control = Enabled] to enable Dynamic Noise Control.
Note:
• When S1-01 = 1, the tolerance to an impact load will decrease compared to V/f Control without Energy Saving.
• You must disable Dynamic Noise Control for applications without an impact load.
The current level increases from the added load and improves the drive responsiveness.
2. Increase S1-02 [Voltage Reduction Rate] to make the flux stronger and increase the torque.
Note:
The Dynamic Noise Control function will decrease the load movement to a minimum level.
3. Decrease S1-03 [Voltage Restoration Level] and S1-04 [Voltage Restoration Off Level] to recover the voltage
more quickly during the impact load conditions.
Note:
Under certain conditions, voltage stability may be unsatisfactory.
4. Decrease S1-05 [Volt Restore Sensitivity Time K] to decrease the voltage level and increase the voltage
restoration speed when the load increase.
5. Decrease S1-06 [Volt Restore Impact Load Time K] to increase drive response to an impact load.
When the output voltage is unstable, increase these values to decrease the load response:
• Difference between S1-03 and S1-04
• S1-05
• S1-06
â–  S1-01: Dynamic Noise Control
No.
(Hex.)
Name Description
Default
(Range)
S1-01
(3200)
Dynamic Noise Control Sets the function that decreases the output voltage in variable torque applications to decrease audible
noise.
1
(0, 1)
0 : Disabled
1 : Enabled

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
BrandYASKAWA
ModelHV600
CategoryDC Drives
LanguageEnglish

Related product manuals