Parameter Details
5
5.7 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 261
Setting Value Function Reference
B9 Disable Pre-charge
273
Setting Value Function Reference
188 and 1A8 Inverse Inputs of 88 and A8
Sets the function of the selected MFDI to operate
inversely. To select the function for inverse input, enter
two digits of 88 or A8 for the “xx” in ”1xx”.
274
■ H1-01: Terminal S1 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-01
(0438)
Terminal S1 Function
Selection
Sets the function for MFDI terminal S1. 40
(3 to 1A8)
■ H1-02: Terminal S2 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-02
(0439)
Terminal S2 Function
Selection
Sets the function for MFDI terminal S2. F
(3 to 1A8)
■ H1-03: Terminal S3 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-03
(0400)
Terminal S3 Function
Selection
Sets the function for MFDI terminal S3. 24
(3 to 1A8)
■ H1-04: Terminal S4 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-04
(0401)
Terminal S4 Function
Selection
Sets the function for MFDI terminal S4. 14
(3 to 1A8)
■ H1-05: Terminal S5 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-05
(0402)
Terminal S5 Function
Selection
Sets the function for MFDI terminal S5. 3
(3 to 1A8)
■ H1-06: Terminal S6 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-06
(0403)
Terminal S6 Function
Selection
Sets the function for MFDI terminal S6. 4
(3 to 1A8)
■ H1-07: Terminal S7 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-07
(0404)
Terminal S7 Function
Selection
Sets the function for MFDI terminal S7. 6
(3 to 1A8)
■ MFDI ON/OFF Time Delay
This function supplies an ON/OFF Delay to all MFDIs. To use this function, set parameters H1-61 to H1-67
[Terminal Sx On-Delay Time] and H1-71 to H1-77 [Terminal Sx Off-Delay Time].