Parameter Details
5
5.13 Y: Application Features
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 407
5.13 Y: Application Features
Y1: Application Basics
Y1-04: Sleep Wake-up Level
No.
(Hex.)
Name Description
Default
(Range)
Y1-04
(3C03)
RUN
Sleep Wake-up Level Sets the level that feedback must be less than for the time set in Y1-05 [Sleep Wake-up Level Delay
Time] to start the system. This level also sets the wake up level when the drive is in Sleep Mode.
When Y1-04 < 0, the feedback level must decrease this amount to less than the setpoint.
0.0
(-999.9 - +999.9)
Note:
When PID operates in reverse mode, the feedback value must increase to more than the start level for the time set in Y1-05 for the system to
start.
When Y2-01 = 5 [Sleep Level Type = Output Frequency (non-PID)], the drive will ignore this parameter.
Set this parameter to 0.0 to disable the function.
Range is 0.00 to 99.99 with sign-bit - or + indicating Delta to Setpoint.
Display unit and scaling change when the system units change.
Y1-05: Sleep Wake-up Level Delay Time
No.
(Hex.)
Name Description
Default
(Range)
Y1-05
(3C04)
RUN
Sleep Wake-up Level Delay
Time
Sets the drive to start the System again when the feedback decreases to less than Y1-04 [Sleep Wake-
up Level] for the time set in this parameter.
1 s
(0 - 3600 s)
Y1-06: Minimum Speed
No.
(Hex.)
Name Description
Default
(Range)
Y1-06
(3C05)
RUN
Minimum Speed Sets the minimum frequency at which the drive will run. The drive applies this setting to HAND and
AUTO modes.
0.0 Hz
Determined by Y1-07
Note:
The unit, decimal place, and setting range change when the Y1-07 [Minimum Speed Units] setting changes:
Y1-07 = 0 [Hz]: The setting range is 0.0 Hz to E1-04 Hz.
Y1-07 = 1 [RPM]: The setting range is 0 RPM to (E1-04 × 60) RPM.
Y1-07: Minimum Speed Units
No.
(Hex.)
Name Description
Default
(Range)
Y1-07
(3C06)
Minimum Speed Units Sets the units and decimal place for Y1-06 [Minimum Speed]. 0
(0, 1)
0 : Hz
1 : RPM
Note:
Changing Y1-07 will set Y1-06 [Minimum Speed] to the default value.
Y1-08: Low Feedback Level
No.
(Hex.)
Name Description
Default
(Range)
Y1-08
(3C07)
RUN
Low Feedback Level Sets the lower detection level for the PID feedback. 0.00%
(0.00 - 99.99%)

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
BrandYASKAWA
ModelHV600
CategoryDC Drives
LanguageEnglish

Related product manuals