Parameter Details
5
5.8 L: Protection Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 317
5.8 L: Protection Functions
L parameters set the following functions.
• Motor Overload Protection
• Operation During Momentary Power Loss
• Stall Prevention
• Speed Detection
• Auto Restart
• Detection of Overtorque/Undertorque
• Torque Limit
• Hardware Protection
â—† L1: Motor Protection
L1 parameters set the motor overload protection function.
â–  L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors. 1
(0, 1)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
• Output Current
• Output Frequency
• Motor thermal characteristics
• Time characteristics
If the drive or bypass board detects motor overload, the drive will trigger an oL1[Motor Overload] or the bypass
board will trigger an FB05 [Motor Overload] and stop output.
Set H2-01 = 1F [Term M1-M2 Function Selection = Motor Overload Alarm (oL1)] to set a motor overload alarm. If
the motor overload level is more than 90% of the oL1 detection level, the output terminal turns ON and triggers an
overload alarm.
0 : Disabled
Disable motor protection when motor overload protection is not necessary or when the drive is operating more than
one motor.
Refer to Figure 5.69 for an example of the circuit configuration to connect more than one motor to one drive.

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control