Parameter List
9
9.9 F: Options
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 611
9.9 F: Options
â—† F6: Communication Options
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive
detects bUS [Option Communication Error].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
1
(0 - 5)
253
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Sets the conditions at which EF0 [Option Card External Fault] is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
254
F6-04
(03A5)
bUS Error Detection
Time
Sets the delay time for the drive to detect bUS [Option Communication Error].
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
2.0 s
(0.0 - 5.0 s)
254
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized
with A1-03 [Initialize Parameters].
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
0
(0, 1)
255
F6-14
(03BB)
BUS Error Auto Reset Sets the automatic reset function for bUS [Option Communication Errors].
0 : Disabled
1 : Enabled
0
(0, 1)
255
F6-15
(0B5B)
Comm. Option
Parameters Reload
Sets the update method when you change F6-xx, F7-xx [Communication Options].
0 : Reload at Next Power Cycle
1 : Reload Now
2 : Cancel Reload Request
0
(0 - 2)
255
â—† F7: Ethernet Options
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-01
(03E5)
IP Address 1 Sets the first octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
192
(0 - 255)
255
F7-02
(03E6)
IP Address 2 Sets the second octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
168
(0 - 255)
255
F7-03
(03E7)
IP Address 3 Sets the third octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
1
(0 - 255)
256
F7-04
(03E8)
IP Address 4 Sets the fourth octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
20
(0 - 255)
256

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
BrandYASKAWA
ModelHV600
CategoryDC Drives
LanguageEnglish

Related product manuals