$GYDQW
&RQWUROOHU8VHU¶V*XLGH
6HFWLRQ 3URFHVV,QWHUIDFH
3BSE 002 415R701 Rev A 1-75
$QDORJ0RGXOHV
The analog I/O modules all have galvanic isolation relative to chassis ground in a group of 4 or
8 channels. The modules have the standard set of module status indicators.
Open circuit detection is available for inputs and outputs configured for 4…20 mA and for the
RTD and TC inputs.
7DEOH 6$QDORJ0RGXOHV
0RGXOHW\SH 'HVFULSWLRQ
AI810 Analog Input 1 x 8 channels. 0(4)…20 mA, 0(2)…10V, 12 bit.,
0.1% Current shunt resistor is protected to 30 V.
Rated isolation voltage 50 V.
AI820 Analog Input differential 1 x 4 channels. -20…20 mA, -5...5 V,
-10…10 V, 12 bit + sign, 0.1 %, CMV 50 V.
Current shunt resistor is protected to 30 V.
Rated isolation voltage 50 V.
AI830 Analog Input 1 x 8 ch. Pt100 (-80... 80
o
C, -200... 250
o
C,
-200 ... 850
o
C), Ni100 (-60 ... 180
o
C), Ni120 (-80 ... 260
o
C),
Cu10 (-100 ... 260
o
C), Resistor (0 ... 400), 14 bit.
Rated isolation voltage 50 V.
AI835 Analog Input 1 x 8 ch. Termo Couples (TC),
type B (0 ... 1820
o
C), type C (0 ... 2300
o
C),
type E (-270 ... 1000
o
C), type J (-210 ... 1200
o
C),
type K (-270 ... 1372
o
C), type N (-270 ... 1300
o
C),
type R (-50 ... 1768
o
C), type S (-50 ... 1768
o
C),
type T (-270 ... 400
o
C), linear -30 .... 75 mV, 14 bit.
Rated isolation voltage 50 V.
AI890 Analog Input, with Intrinsically safe interface 1 x 8 ch.
0 (4)...20mA, 12 bit, 0.1%
Rated isolation voltage 50 V.
AI895 Analog Input, with Intrinsically safe and HART interface,
0(4)...20mA, 12 bit, 0.1%
Rated isolation voltage 50 V.
AO810 Analog Output 1 x 8 channels, 0(4)…20 mA, 14 bit 0.1%
RL maximum 500/850 Ohms.
Rated isolation voltage 50 V.
AO820 Analog Output 4 x 1 channels, -20…20 mA, -10...10 V,
12 bit + sign, 0.1%, individually galvanical isolated.
Current output RL maximum 550 Ohms.
Voltage output RL minimum 2 kohms.
Rated isolation voltage 50 V.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals