Advant
®
Controller 450 User’s Guide
Section 5.5.2 Diagnostics and Fault Announcement
3BSE 002 415R701 Rev A 5-15
DIAGN
n
DIAGN
2
Reference in Advant Cont roller 400 Display:
Presentation:
Function:
Actions at fault:
Block Diagram:
(I/O) 24 V supply A/B
green Normal
red cr Fault - Lost voltage or lost redundancy
Supervision of the 24 V power supply for one or several I/O subracks (collecting alarm).
Plain System Message
at fault:
10
Each branch A/B is supervised if redundant branches are installed.
Hardware
POW SUPP ST 24 V I/O supply A/B faulty Net xx Nod yy
Software
DB; AC450
System status OS
24 V supply A
IO24VA_ERR
Y/N
IO24VA
DSSS 171
A
B
24VA
24VB
24 V distribution
I/O Power SupplyTC520
A1
DIAGN.
DIAGN.
A2
AG
0V
I/O Subrack
n
2
1
Fault
24 V
DIAGN.
1)
1) If the inputs A1, A2 are applied to I/O 24 V
Supply A/B supervision then the F1, F2
terminals on the AC450 data base element
must be set to NO. (That is the indication
F1, F2 deleted).
AC450 Cabinets
X1 X 1
X2
X2
FA FA
FB
FB
TC560V1
Distributed I/O Cabinets
TC561V1
DSSS 171
DIAGN
24 V A
24 V B
1
I/O Subrack
24 V distribution
1 See Section 5.4.9.5, Check of Power Supply

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals