Advant
®
Controller 450 User’s Guide
Section 2.2.10 S100 I/O
3BSE 002 415R701 Rev A 2-35
If for some reason the cabinets are not arranged side by side then the bus extension cable must
be routed separated from other cables (>100 mm). A CE-marked design put the requirement that
the extension cable shield is additionally grounded by the cable clamp in the cabinet floor.
Functional Measures
Address Jumpering (DSBC 174, DSBC 176)
The jumpering group S1 defines the boards I/O address. Instructions on how to set a bus
extender board address are given in the S100 I/O Hardware Reference Manual.
Functional Jumpering
All jumpers in jumper group S3 on DSBC 174 are open when the bus extender is used in
systems based on CPU PM511 (and closed when used in systems based on CPU PM510).
Preparation for Start-up
Please see the general checklist in Section 2.2.15, Checklists.
2.2.10 S100 I/O
Assembly
Circuit boards and connection units are normally factory assembled. For information regarding
the location of equipment, see the actual delivery documentation. Assembly drawings,
for example, also give the cross-reference between the following structures:
Physical location of circuit boards and connection units
Functional item designation of circuit boards and signal channels
Board address.
The functional item designation, for example, AI1 and the board hexadecimal address, H’20 are
hard related to each other and supported by the configuration tool when creating the data base.
(Normally, this relation is never changed.) However, the relation to the physical location is
determined when the equipment to be delivered is designed. Initially, standard location is
followed, see Section 2.1.4, Standard Layout and Disposition of Cabinets. Customized layout is
possible whenever applicable.
Reorganization of boards and connection units is “theoretically” possible. I/O board addresses
are not hard related to physical location. The board itself is carrying the address. The question
is, are there sufficient cable lengths (board-connection unit) to do the work?
A reorganization also calls for changing the documentation of the equipment.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals