Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-2 3BSE 002 415R701 Rev A
The free space in front of cabinets. Also reflect on how much space is required to fully
open either a left-hand or right-hand hinged cabinet door (both exist). There must always
be space left for safety reasons even with open doors.
Spare area for future enlargement of the equipment.
A well-developed process connection, with or without marshalling facilities.
Grounding by an effective net of copper bars.
Cable routing with respect to installation rules.
Availability of power and other utilities.
Standards and legal regulations to be followed.
The following sections examine some of these factors in detail and provide recommendations
and requirements as necessary.
2.1.2 Environmental Considerations
General
The Advant Controller system is designed for a demanding industrial environment. Alternative
cabinetry is available for different degrees of protective rating (IP21, IP41, IP54). Interference
from electrical sources is suppressed by a suitable solid design and particular installation rules.
Equipment is to be located in a control room or an electric room or distributed in the process
area.
The common requirements for the building where the system is to be stored or installed are:
NOTE
The building should provide an environment such that established
environmental conditions are not normally exceeded.
The environmental conditions which Advant OCS products are designed to withstand, during
storage and transport as well as during operation, are specified in a separate environmental data
sheet. Limit values are given to: Corrosive gases, Temperature, Vibration, Moisture, Electro-
Magnetic Compatibility, and so on.
Most applications need no special arrangement. Standard cabinetry and installation according to
the rules suffice. Occasionally, you must consider special protection with respect to particular
situations.
Sealed cabinets are a good basic solution to prevent damage to electronic equipment from,
for example, corrosive gases, moisture and dust. However, sealing prevents the normal cooling
resulting from self-convection or forced cooling by a fan. In turn, this reduces, to a large extent,
the heat dissipation permitted in a cabinet.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals