Page #89 background image
$GYDQW
&RQWUROOHU8VHU¶V*XLGH
6HFWLRQ 3URFHVV,QWHUIDFH
3BSE 002 415R701 Rev A 1-59
Each board has built-in reference channels for automatic calibration and testing.
The data base is updated by scanning, with cycle times normally selected from the range
100 ms to 600 s.
The suppression frequency is selectable from 20, 30, 50 and 60 Hz.
The current generators for sensors deliver 2.5 mA, in accordance with DIN 43760.
Optional software filtering and deadband limits for updating can be selected.
$QDORJ,QSXWIRU7KHUPRFRXSOH0DLQ3RLQWV
Thermocouple inputs are available for different sensor types.
Each board has built-in reference channels for automatic calibration and testing.
The data base is updated by scanning, with cycle times normally selected from the range
100 ms to 600 s.
Optional software filtering and deadband limits for updating can be selected.
$QDORJ,QSXW%RDUG7\SHV
Table 1-15 presents available analog input boards.
7DEOH $QDORJ,QSXW%RDUGV
%RDUGW\SH 'HVFULSWLRQ &RQQHFWLRQXQLW &DEOH
DSAI 130 16 channels, differential inputs, resolution
12 bits + sign,
0 to ±10 V, 0 to ±5 V,
0 to ±2.5 V, 0 to ±1.25 V or
0 to ±20 mA, 0 to ±10 mA, 0 to ±5 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.1%, CMV 100 V
DSTA 131 DSTK 221L3
DSAI 130A 16 channels, differential inputs, resolution
12 bits + sign,
0 to ±10 V, 0 to ±5 V,
0 to ±2.5 V, 0 to ±1.25 V or
0 to ±20 mA, 0 to ±10 mA, 0 to ±5 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.1%, CMV 50 V
DSTA 131 DSTK 221L3
DSAI 130 Eight differential and eight directly grounded inputs
(single ended), transducer supply fused channel by
channel, resolution 12 bits,
0 to ±10 V, 0 to ±5 V,
0 to ±2.5 V, 0 to ±1.25 V or
0 to ±20 mA, 0 to ±10 mA, 0 to ±5 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.1%, CMV 100 V
DSTA 133 DSTK 221L3

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals