$GYDQW
&RQWUROOHU8VHU¶V*XLGH
&KDSWHU ,QWURGXFWLRQ
1-60 3BSE 002 415R701 Rev A
DSAI 130A 16 differential and eight directly grounded inputs
(single ended), transducer supply fused channel by
channel, resolution 12 bits,
0 to ±10 V, 0 to ±5 V,
0 to ±2.5 V, 0 to ±1.25 V or
0 to ±20 mA, 0 to ±10 mA, 0 to ±5 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.1%, CMV 50 V
DSTA 135 DSTK221L3
DSAI 130 16 channels, differential inputs, resolution
12 bits + sign,
0 to ±10 V, 0 to ±5 V,
0 to ±2.5 V, 0 to ±1.25 V or
0 to ±20 mA, 0 to ±10 mA, 0 to ±5 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.1%, CMV 100 V
DSTA 137
provides object
oriented
connection to
DSAI 130 and
DSAO 130
DSTK 150
DSAI 130A 16 channels, differential inputs, resolution
12 bits + sign,
0 to ±10 V, 0 to ±5 V,
0 to ±2.5 V, 0 to ±1.25 V or
0 to ±20 mA, 0 to ±10 mA, 0 to ±5 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.1%, CMV 50 V
DSTA 138
provides object
oriented
connection to
DSAI 130A and
DSAO 130A
DSTK 150
DSAI 133 32 channels, directly grounded inputs (single
ended), transducer supply fused channel by
channel, resolution 12 bits unipolar,
0 to + 10 V, 0 to + 5 V, 0 to + 20 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.05%
2 x DSTA 002A DSTK 222L3
DSAI 133A 32 channels, directly grounded inputs (single
ended), transducer supply fused channel by
channel, resolution 12 bits unipolar,
0 to + 10 V, 0 to + 5 V, 0 to + 20 mA,
4 to 20 mA (elevated zero obtained by SW)
shunt 250 0.05%
2 x DSTA 002B DSTK 222L3
2 x DSAI 133 DSAI 133 in redundant coupling. Data otherwise the
same as for DSAI 133 above.
2 x DSTA 002A
(1)
2 x DSTK 222L3
2 x DSAI 133A DSAI 133 in redundant coupling. Data otherwise the
same as for DSAI 133 above.
2 x DSTA 002B
(1)
2 x DSTK 222L3
DSAI 146 31 channels (+ one ref. channel) for Pt100,
three-wire, resolution, 12 bits + sign,
-100 to +320°C or -200 to +640°C
DSTA 145 DSTK 229SL3
7DEOH $QDORJ,QSXW%RDUGV&RQWLQXHG
%RDUGW\SH 'HVFULSWLRQ &RQQHFWLRQXQLW &DEOH

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals