Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-54 3BSE 002 415R701 Rev A
2.4.2.1 Power-up
If, for some reason, you desire a limited power-up, the minimum equipment necessary is:
Processor Module PM511 including a program card
Submodule Carrier SC5x0.
1. Check that the circuit breakers on the power switch units are switched off.
There is one circuit breaker for mains A (labeled S1) and one for mains C (labeled F1).
Redundancy adds another circuit breaker for mains B (labeled S1).
Reflect the relevance of:
Power switch in the cabinet housing the controller subrack
Separate power switch in any cabinet housing S100 I/O subrack with object oriented
connection units (OOCU)
Separate power switch in physically distributed cluster of S100 I/O subrack.
2. Set the start mode selector on Processor Module PM511 in 3 (CLEAR) position.
NOTE
The CLEAR position is the only possible choice when you power up for the
first time.
Repeat for an eventually redundant processor module.
3. Set the switch on all bus extenders DSBC 174 in position RUN.
4. Switch on the mains supply to the cabinet and check for correct mains voltage with a
multimeter at the connection terminals on the power switch unit. See the terminal diagram
form enclosed at delivery.
5. Switch on the circuit breaker S1 on the power switch unit(s) in any order (mains A and B).
Also switch on the miniature circuit breaker F1 for mains C.
Several power switch and distribution units can exist in the controller cabinet or in
adjacent I/O cabinets.
6. Check for the following positive indications of a successful power-up:
Distribution Unit SX554 green LED LIVE (24 V)
Regulator SR511 green LEDs 5 V and 2 V
Backup Power Supply SB511 (or SB510) green LED IP
Processor Module PM511 green LED RUN
display ind. P2
(Indicating working mode P2, CONFIGURATION)
S100 I/O Bus Extenders DSBC 174 or DSBC 176 green LEDs RUN
and DC OK
Redundant Processor Module PM511 (BACKUP) green LED RUN
display ind. b2...b1
(The backup unit starts in working mode b2, UPGRADING. After a while (<90s)
there is a transition to b1, STANDBY). If a redundant processor module is available,
and if both modules’ start mode selectors are set in 3 (CLEAR) position, then the left

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals