&RQWUROOHU8VHU¶V*XLGH
6HFWLRQ 3RZHU6XSSO\
3BSE 002 415R701 Rev A 1-41
0DLQV1HW)LOWHU
The CE-marked design provides a mains net filter for each supply A, B and C. The filter is
installed between the enclosure port and the mains power switch. The purpose is to minimize
the risk of interference and the emission of conducted radio frequency field.
The filter is adapted to the estimated load from the installed equipment.
0DLQV3RZHU6ZLWFKDQG'LVWULEXWLRQ
You use the power switch and distribution unit to connect and disconnect the
Advant Controller 450 system to the mains and for distribution of voltage to different units in
the cabinet. The power switch unit contains terminal blocks, miniature circuit breakers and
power outlets for, for example, power supply units.
Normally, a common circuit breaker disconnects the mains from all cabinets housing the
controller and the I/O installation, that is the “hard” related cabinets. Variants can exist. Please
refer to the actual delivery documentation for further information.
3RZHU6XSSO\
The power supply units provide the regulators in the subracks with 24 V unstabilized d.c.
voltage. They can also be used to supply other circuits which do not require stabilized 24 V
voltage such as sensors, indicators, and so on.
There are certain restrictions on utilizing a common power supply for the system itself and
external equipment. Please refer to Section 3.1, Design Considerations.
Use duplicated power supply units to provide redundancy.
Varying requirements on power supply are met by a range of supply modules with different
technical data. You can select according to Table 1-12.
7DEOH 6HOHFWLRQ*XLGHRI3RZHU6XSSO\0RGXOHV
0RGXOHW\SH DFGF 1HW 0D[ORDG 5HPDUNV
SA161 a.c. 120 V 24 V, 10 A
SA162 a.c. 230 V 24 V, 10 A
SA167 a.c. 120 V 24 V, 25 A
SA168 a.c. 230 V 24 V, 25 A
SD150 d.c. 24-48 V d.c. 24 V, 20 A
SA171 a.c. 120 V 48 V, 5 A For field equipment only
SA172 a.c. 230 V 48 V, 5 A For field equipment only

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals