$GYDQW
&RQWUROOHU8VHU¶V*XLGH
&KDSWHU ,QWURGXFWLRQ
1-110 3BSE 002 415R701 Rev A
3URJUDP([HFXWLRQ&KHFN
Execution check by “watchdog” is carried out with respect to three priority levels.
Task reference, supervision time and consequences at exceeded time are given below:
Timer task - 100 ms - safety shut-down
Application program - 5 s - safety shut-down
Idle task - 30 minutes - system message about a system too heavily loaded.
'LDJQRVWLFRI,20RGXOHV
All I/O modules are checked regarding missing hardware or errors in the addressing logic.
It is common to all I/O modules that, if any error is detected, an alarm and a message go to the
operator. The error is also indicated with a red LED on the front of the board. The application
program handles necessary actions via the data base. Different types of I/O modules have
adapted diagnostics and error handling. For further information on this topic, see Chapter 5,
Maintenance.
'LDJQRVWLFRI3RZHU6XSSO\
Supervision of the internal 24 V supply and the stabilized 5 V supply
Applicable supervision of power supply for sensors
Supervision of the battery backup supply.
2WKHU'LDJQRVWLFVDQG(UURU+DQGOLQJ
Adequate diagnostics and error handling are also available/possible for the following equipment
and functions:
Communication links
Terminal/printer connection
•Fans
Redundant functions in general.
6XSHUYLVLRQ0RGXOH
The System Status Collector TC520 in the controller subrack performs certain system
supervision. Diagnostic signals from power supply units and fans within the cabinets are
connected to TC520.
The front connector of TC520 provides the connection for four extra user-defined supervisory
signals (24 V). Two of them are intended to be used for redundant I/O voltage supply
supervision. The signal cables may not be extended outside the controller cabinets due to the
risk of interference.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals